Round Series Split Core Current Transformer
The JIANGYIN SPARK series of split core current transformer are designed for fast and easy installation.The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken offline and disconnected for CT installation.This method permits a safer,easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary
Specifications
Rated Current 5A to 1000Amp.
Output of 0.333 Volt at rated current
Accuracy ± 1% from 10% to 150% of Full Scale Range
Phase angle < 2 maximum at 50% rated current
Snap closing/opening feature.
Shrouded core blades for protection during installation.
Core interleaved at joints for accuracy.
No exposed metal parts on assembled transformer.
Internal precision burden resistor across secondary.
Epoxy encapsulated housing.
Accuracy is measured from 10% to 130% of rated current.
Phase angle is measured at 50% of rated current
Model | Input | Ratio | Output | Error | Dimensions | ||
OD | ID | H | |||||
A | mV | % | mm | mm | mm | ||
XH-SCT-T12 | 10-30 | 1000-3000 | 333-5000 | 0.5-1.0 | 40 | 12 | 19.5 |
XH-SCT-T25 | 20-200 | 67 | 25 | 19 |
Model | Input | Out pu | Error | Dimensions | ||
OD | ID | H | ||||
A | mV | % | mm | mm | mm | |
XH-SCT-T33 | 600 | 300 | 0.5-1.0 | 104 | 33 | 43.5 |
Model | Input | Ratio | Output | Error | Dimensions | ||
OD | ID | H | |||||
A | T | mA | % | mm | mm | mm | |
XH-SCT-T70 | 50-1000A | 1000-3000 | 50-1000 | 05 | 160 | 70 | 32 |